Manual link for MPP Solar LV6548
Manual link for RICH RS-H6548
*NOTES: MPP Solar LV6548 and RICH RS-H6548 is basically the same model
TABLE OF CONTENTS:
1 Product Overview
2 General Wiring Details
3 Parallel Operations
- 3.1 Single Phase Wiring + Commissioning Steps
- 3.2 Split Phase Wiring + Commissioning Steps
4 Settings
Product Overview
General Wiring Details
WARNING: It's REQUIRED to connect battery for parallel operation.
The cable size of each inverter is shown as below:
Recommended battery cable and terminal size for each inverter:

WARNING: Be sure the length of all battery cables is the same. otherwise, there will be voltage difference between inverters and battery cables to cause parallel inverters not working.
Recommended AC input and output cable size for each inverter:
Model
|
AWG no.
|
Torque
|
LV 6548
|
4 AWG
|
1.4 ~16 Nm
|
You need to connect the cables of each inverter together. Take the battery cables for example: You need to use a connector or bus-bar as a joint to connect the battery cables together, and then connect to the battery terminal. The cable size used from joint to battery should be X times cable size in the tables above. "X" indicates the number of inverters connected in parallel.
Regarding AC input and output, please follow the same principle.
CAUTION: Please install the breaker at the battery and AC input side. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of battery or AC input.
Recommended breaker specification of battery for each inverter:
Model
|
1 Unit*
|
LV 6548
|
250A/70VDC
|
*If you want to use only one breaker at the battery side for the whole system, the rating of the breaker should be X times current of 1 unit. "X" indicates the number of inverters connected in parallel.
Recommended breaker specification of AC input with single phase:
Model
|
2 units
|
3 units
|
4 units
|
5 units
|
6 units
|
LV 6548
|
120A/230VAC
|
180A/230VAC
|
240A/230VAC
|
300A/230VAC
|
360A/230VAC
|
NOTE 1: Also, you can use 60A breaker with only 1 unit ang install one breaker at its AC input in each inverter
NOTE 2: Regarding three-phase system, you can use 4-pole breaker directly and the rating of the breaker should be compatible with the phase current limitation from the phase with maximum units.
Recommended battery capacity
Inverter Parallel Numbers
|
2
|
3
|
4
|
5
|
6
|
Battery Capacity
|
200Ah
|
400Ah
|
400Ah
|
600Ah
|
600Ah
|
WARNING: Be sure that all inverters will share the same battery bank. Otherwise, the inverters will transfer to fault mode.
Parallel Operations in Single Phase
WIRING DIAGRAM

NOTES:
1. For RICH model, please refer to page 47 for more inverters in parallel.
2. For MPP SOLAR model, please refer to page 46 for more inverters in parallel.
COMMISSIONING STEPS
Parallel Operations in Split Phase
WIRING DIAGRAM

NOTES:
For RICH model, please refer to page 54 for more inverters in parallel.
For MPP SOLAR model, please refer to page 53 for more inverters in parallel.
COMMISSIONING STEPS

Settings
After completing the physical setup, please follow the complete LCD settings below. Kindly note that this is only for our kit's intended use of split phase 240/120V configuration in an off grid or with hybrid charging setup. Some settings will vary depending on actual usage/purpose on site.
After pressing and holding ENTER button for 3 seconds, it will enter setting mode. Press “UP” or “DOWN” button to select setting programs. Then press “ENTER” button to confirm the selection or ESC button to exit.
COMMON SETTINGS:
00 - ESC
01 - SbU
02 - 60
03 - APL
06 - Lrd
07 - trd
09 - 60
10 - 120
11 - 45
12 - 44.5
13 - FUL
16 - SNU
18 - bON
19 - ESP
20 - LON
22 - AON
23 - bYd
25 - FEN
28 - //Please see Parallel Operation Setup guide above
30 - EdS
31 - 58.4
33 - 60
34 - 120
35 - 30d
36 - AdS
37 - Nrt
41 - ddS
51 - LEN
52 - NOr
53 - NOr
54 - SOL //Check manual to change the RGB LED effects
55 - C01
92 - dCE
93 - Nrt
94 - 10
95 - //time setting - minute
96 - //time setting - hour
97 - //time setting - day
98 - //time setting - month
99 - //time setting - year
FOR BigBattery 48V LITHIUM GRIZ
05 - USE
26 - 58.4
27 - 58.4
29 - 44
FOR BigBattery 48V LITHIUM KONG ELITE
05 - USE
26 - 58.4
27 - 58.4
29 - 44
FOR BigBattery 48V LITHIUM WHITE RHINO
05 - USE
26 - 58.4
27 - 58.4
29 - 44