When setting up your inverter, it will be important to set the parameters properly based on the battery that you have with your system.
Please go through and switch the settings to the parameters below:
For your LV6048 Inverter, go to settings by pressing and holding for 3 sec the enter button, Navigate to the following settings and change to the following parameters:
For Batteries KONG ELITE, KONG, HSKY, TREX & GRILA
• Settings 05: Battery Type - USE (User-define)
• Settings 02: Max Charging Current - 90A
• Settings 11: Max Utility Charging Current - 40A
• Settings 26: Bulk Charging Voltage - 58.4V
• Settings 27: Float Charging Voltage - 58.0V
• Settings 29: Low DC Voltage Cut-off - 48.0V
The max input voltage of the charge controller in your unit is from 90V - 230V. This means that you need AT LEAST 90V going into the unit to register a charge. What is super cool about the LV6548 with the huge charge controller is that you can get roughly 8000 watt into the unit.
If you have added more panels, or have them set-up incorrectly, it can cause your system to shut down and restart. Setting 6 is designed so that in the event of an overload, the system shuts off and reboots. This is a friendly reminder that it is important to follow the diagram instructions provided, or make sure to stay within the input voltage of the unit. You can find the diagram instructions below depending on the kit you ordered.